We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
3RF2310-1AA45 | 3RF2320-1AA45 | 3RF2330-1AA45 | 3RF2340-1AA45 | 3RF2350-1AA45 | ||
GENERAL TECHNICAL DATA: | UNITS | |||||
Product brand name | SIRIUS | SIRIUS | SIRIUS | SIRIUS | SIRIUS | |
Product designation | Solid-state | Solid-state | Solid-state | Solid-state | Solid-state | |
contactor | contactor | contactor | contactor | contactor | ||
Product function | Zero-point | Zero-point | Zero-point | Zero-point | Zero-point | |
switching | switching | switching | switching | switching | ||
Number of poles / for main current circuit | 1 | 1 | 1 | 1 | 1 | |
Protection class IP | IP20 | IP20 | IP20 | IP20 | IP20 | |
Ambient temperature | ||||||
• during operating | °C | -25 … +60 | -25 … +60 | -25 … +60 | -25 … +60 | -25 … +60 |
• during storage | °C | -55 … +80 | -55 … +80 | -55 … +80 | -55 … +80 | -55 … +80 |
Installation altitude / at height over | m | 1,000 | 1,000 | 1,000 | 1,000 | 1,000 |
Sea level / maximum | ||||||
Resistance against vibration / according | 2g | 2g | 2g | 2g | 2g | |
to IEC 60068-2-6 | ||||||
Resistance against shock / according | 15g / 11 ms | 15g / 11 ms | 15g / 11 ms | 15g / 11 ms | 15g / 11 ms | |
to IEC 60068-2-27 | ||||||
Reference code | ||||||
• according to DIN 40719 extended | K | K | K | K | K | |
according to IEC 204-2 / | ||||||
according to IEC 752 | ||||||
• according to DIN EN 61346-2 | Q | Q | Q | Q | Q | |
Number of NC contacts / for auxiliary | 0 | 0 | 0 | 0 | 0 | |
contacts | ||||||
Number of NO contacts / for auxiliary | 0 | 0 | 0 | 0 | 0 | |
contacts | ||||||
Number of changeover contacts / for | 0 | 0 | 0 | 0 | 0 | |
auxiliary contacts | ||||||
MAIN CIRCUIT: | ||||||
Number of NO contacts / for main contacts | 1 | 1 | 1 | 1 | 1 | |
Number of NC contacts / for main contacts | 0 | 0 | 0 | 0 | 0 | |
Operating Current | ||||||
• at AC-1 / at 400 V / rated value | A | 10.5 | 20 | 30 | 40 | 50 |
• at AC-51 / rated value | A | 10.5 | 20 | 30 | 40 | 50 |
Operating current / minimum | mA | 100 | 500 | 500 | 500 | 500 |
Operating voltage | ||||||
• at 50 Hz / at AC / rated value | V | 48 … 600 | 48 … 600 | 48 … 600 | 48 … 600 | 48 … 600 |
• at 60 Hz / at AC / rated value | V | 48 … 600 | 48 … 600 | 48 … 600 | 48 … 600 | 48 … 600 |
Working range relative to the operating | ||||||
voltage | ||||||
• at 50 Hz / with AC | V | 40 … 660 | 40 … 660 | 40 … 660 | 40 … 660 | 40 … 660 |
• at 60 Hz / with AC | V | 40 … 660 | 40 … 660 | 40 … 660 | 40 … 660 | 40 … 660 |
Operating frequency | ||||||
• rated value | Hz | 50 … 60 | 50 … 60 | 50 … 60 | 50 … 60 | 50 … 60 |
Insulation voltage / rated value | V | 600 | 600 | 600 | 600 | 600 |
Voltage slew rate / at the thyristor / for | V/µs | 500 | 1000 | 1000 | 1000 | 1000 |
main contacts / maximum permissible | ||||||
Block voltage / at the thyristor / for main | V | 1,200 | 1,200 | 1,200 | 1,200 | 1,200 |
contacts / maximum permissible | ||||||
Reverse current / of the thyristor | mA | 10 | 10 | 10 | 10 | 10 |
Derating temperature | °C | 40 | 40 | 40 | 40 | 40 |
Active power loss / total / typical | W | 11 | 20 | 33 | 44 | 54 |
Resistance against the impulse current / | A | 200 | 600 | 600 | 1,200 | 1,150 |
rated value | ||||||
I2t-level / maximum | A²·s | 200 | 1,800 | 1,800 | 7,200 | 6,600 |
CONTROL CIRCUIT/CONTROL: | ||||||
Voltage type / of control feed voltage | DC | DC | DC | DC | DC | |
Control supply voltage / 1 | ||||||
• for DC | ||||||
• initial rated value | V | 4 | 4 | 4 | 4 | 4 |
• final rated value | V | 30 | 30 | 30 | 30 | 30 |
Control supply voltage | ||||||
• for DC / final value for | V | 1 | 1 | 1 | 1 | 1 |
signal<0>-recognition | ||||||
Control current | ||||||
• for DC / rated value | mA | 20 | 20 | 20 | 20 | 20 |
Fuse assignments: | https://www.automation.siemens.com/cd-static/material/info/3RF23_eng.pdf | |||||
INSTALLATION/MOUNTING/ DIMENSIONS: | ||||||
Mounting type | Screw and snap-on mounting onto 35mm standard mounting rail | |||||
Mounting type / series installation | Yes | Yes | Yes | Yes | Yes | |
Design of the thread / of the screw for | M4 | M4 | M4 | M4 | M4 | |
fastening of the operating resource | ||||||
Tightening torque / of the screw for | N·m | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 |
fastening of the operating resource | ||||||
Width | mm | 22.5 | 22.5 | 45 | 67.5 | 67.5 |
Height | mm | 100 | 100 | 100 | 100 | 100 |
Depth | mm | 94 | 140.5 | 140.5 | 156 | 156 |
CONNECTIONS/TERMINALS: | ||||||
Design of the electrical connection / for the | screw-type | screw-type | screw-type | screw-type | screw-type | |
main current circuit | terminals | terminals | terminals | terminals | terminals | |
Design of the thread / of the connection | M4 | M4 | M4 | M4 | M4 | |
screw / for main contacts | ||||||
Tightening torque / for main contacts | ||||||
• with screw-type terminals | N·m | 2 … 2.5 | 2 … 2.5 | 2 … 2.5 | 2 … 2.5 | 2 … 2.5 |
Tightening torque (lbf-in) / for main contacts | ||||||
• with screw-type terminals | lbf·in | 18 … 22 | 18 … 22 | 18 … 22 | 18 … 22 | 18 … 22 |
Type of the connectable conductor | ||||||
cross-section | ||||||
• for main contacts | ||||||
• solid | 2x (1.5 … 2.5 mm²), | 2x (1.5 … 2.5 mm²), | 2x (1.5 … 2.5 mm²), | 2x (1.5 … 2.5 mm²), | 2x (1.5 … 2.5 mm²), | |
2x (2.5 … 6 mm²) | 2x (2.5 … 6 mm²) | 2x (2.5 … 6 mm²) | 2x (2.5 … 6 mm²) | 2x (2.5 … 6 mm²) | ||
• finely stranded | ||||||
• w/ conductor end processing | 2x (1 … 2.5 mm²), | 2x (1 … 2.5 mm²), | 2x (1 … 2.5 mm²), | 2x (1 … 2.5 mm²), | 2x (1 … 2.5 mm²), | |
2x (2.5 … 6 mm²), | 2x (2.5 … 6 mm²), | 2x (2.5 … 6 mm²), | 2x (2.5 … 6 mm²), | 2x (2.5 … 6 mm²), | ||
1x 10 mm² | 1x 10 mm² | 1x 10 mm² | 1x 10 mm² | 1x 10 mm² | ||
• for AWG conductors | ||||||
• for main contacts | 2x (14 … 10) | 2x (18 … 14) | 2x (14 … 10) | 2x (14 … 10) | 2x (14 … 10) | |
• for auxiliary and control contacts | 1x (AWG 20 … 12) | 1x (AWG 20 … 12) | 1x (AWG 20 … 12) | 1x (AWG 20 … 12) | 1x (AWG 20 … 12) | |
• for auxiliary and control contacts | ||||||
• solid | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | |
2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | ||
• finely stranded | ||||||
• w/ conductor end processing | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | |
2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | ||
• w/out conductor final cutting | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | 1x (0.5 … 2.5 mm²), | |
2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | 2x (0.5 … 1.0 mm²) | ||
Conductor cross section that can be | ||||||
connected | ||||||
• for main contacts | ||||||
• single- or multi-stranded | mm² | 1.5 … 6 | 1.5 … 6 | 1.5 … 6 | 1.5 … 6 | 1.5 … 6 |
• stranded wire | ||||||
• w/ conductor end processing | mm² | 1 … 10 | 1 … 10 | 1 … 10 | 1 … 10 | 1 … 10 |
• for auxiliary and control contacts | ||||||
• solid | mm² | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 |
• stranded wire | ||||||
• w/ conductor end processing | mm² | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 |
• w/out conductor final cutting | mm² | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 | 0.5 … 2.5 |
AWG number / as coded connectable | 14 … 10 | 14 … 10 | 14 … 10 | 14 … 10 | 14 … 10 | |
conductor cross section / for main contacts | ||||||
Design of the electrical connection / for | screw-type | screw-type | screw-type | screw-type | screw-type | |
auxiliary and control current circuit | terminals | terminals | terminals | terminals | terminals | |
Design of the thread / of the connection | M3 | M3 | M3 | M3 | M3 | |
screw / of the auxiliary and control pins | ||||||
AWG number / as coded connectable | ||||||
conductor cross section | ||||||
• for auxiliary and control contacts | 20 … 12 | 20 … 12 | 20 … 12 | 20 … 12 | 20 … 12 | |
Skinning length / of the cable / for main | mm | 7 | 7 | 7 | 7 | 7 |
contacts | ||||||
Skinning length / of the cable / for | mm | 7 | 7 | 7 | 7 | 7 |
auxiliary and control contacts | ||||||
Tightening torque / for auxiliary and control contacts | ||||||
• with screw-type terminals | N·m | 0.5 … 0.6 | 0.5 … 0.6 | 0.5 … 0.6 | 0.5 … 0.6 | 0.5 … 0.6 |
Tightening torque (lbf-in) / for auxillary | ||||||
and control contacts | ||||||
• with screw-type terminals | lbf·in | 4.5 … 5.3 | 4.5 … 5.3 | 4.5 … 5.3 | 4.5 … 5.3 | 4.5 … 5.3 |
CERTIFICATES/APPROVALS | ||||||
General Product Approval | EMC | Declaration of Conformity |